MP-8  No screw function. The screw cold start prevent wasn’t working on the front zone controller. We replaced the controller & it’s working fine.

          I’ll take the old one to Craig & see if he can fix it.

 

New Novatec dryer – I installed the new motor & speed controller & set the speed at about 8 rph. I dry cycled it for 5 hours & gave it back to them.

 

MP-16  No nozzle heat. I checked the heater bands & power from the contactor. The only thing I saw was one heater wire that may not have had a good connection

       at the wire nut. OK now.

 

Matsui dryer on MP-14 was in high heat alarm. It wouldn’t clear so I powered it down. When it came back on I let the regen. heat come up before I hit the

       Dry button; the process heat came up & it’s running fine. I think they had just moved this dryer & didn’t let it cool down.

 

MP-15  The nozzle was freezing off & it blew out one time. “ Delrin”   They had a 1” band on a 2” nozzle tip & it was slid all the way back. I put a 2” band

       on it & cleaned up the t.c. wire.